Permit Number: T08CM00030
Parcel: 127035160

Address:
5740 E BAKER ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM00030
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2008 GERRY KOZIOL WWM REVIEW Approved
01/16/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/04/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T08CM00030

2/6/08/ 5740 E. BAKER ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

PLUMBING PLANS:

1. NOT MORE THAN ONE TRAP IS PERMITTED ON THE TRAP ARM AT THE KITCHEN SINK. SEE UPC 1001.1

2. GAS: PROVIDE THE TOTAL DEVELOPED LENGTH OF LINE TO THE MOST REMOTE GAS APPLIANCE, THE TOTAL BTU DEMAND OF EACH APPLIANCE,, PER UPC 1217.2

3. THE DISTANCE BETWEEN THE KITCHEN SINK VENT AND THE SINK'S TRAP APPEARS TO EXCEED 5'. SEE UPC 1002.2 . A "FOOT VENT" OR A "CHICAGO LOOP" IS FREQUENTLY USED HERE IF AN "AIR ADMITTANCE VALVE" ISN'T USED. SEE UPC 909.0

ELECTRICAL PLANS:

1. THE RECEPTACLES AT THE KITCHEN COUNTER TOPS APPEAR TO BE OVER SPACED. SEE E3801.4.1

2. PLEASE PROVIDE A RECEPTACLE WITHIN 6' OF THE SOUTH JAMB OF THE EAST EXTERIOR DOOR. SEE E3801.2.1

3. PLEASE SHOW BOTH CIRCUITS 1 AND 3 AS SERVING THE DRYER.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910

Final Status

Task End Date Reviewer's Name Type of Review Description
02/06/2008 GERARDO BONILLA OUT TO CUSTOMER Completed