Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM00024
Review Name: POST 3RD PARTY REVIEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2008 TERRY STEVENS ZONING REVIEW Denied 08/06/2008

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
07/31/2008 MARTIN BROWN FIRE REVIEW Denied Please include the following design criteria to the plan.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
Also, Tucson Fire deparment would prefer that NO backflow preventer is on stalled on the fire service line (sheet P-15)
Additionally, TFD would prefer that no dry systems are installed. Freezing is not a problem in this area, and dry systems create delay in operation of sprinklers.
08/04/2008 GERRY KOZIOL WWM REVIEW Denied 1:HILTON GARDEN INN @ PARK PLACE MALL-1201 FU SFR RATE FOR ROOMS- 349 FU @ COMMERCIAL RATE FOR COMMON AREA
2: NEED TO PERMIT ON-SITE PRIVATE SEWER S04318
3:NEED WASTEWATER 8TH FLOOR REVIEW OF FUTURE DINING ROOM WATER FEATURE DRAIN TO PUBLIC SEWER - KURT @ 740-6500
08/04/2008 ROBERT SHERRY WATER REVIEW Approved
08/06/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied Unable to approve Building Plan at this time. Development Plan must be approved prior to approval of Building Plan.


If you have any question please feel free to contact me at 837-4928 or bianca.ramirez@tucsonaz.gov

Bianca Ramirez
08/06/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2008 GERARDO BONILLA REJECT SHELF RECEIVED