| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2008 | SUE REEVES | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/25/2008 | DAVE MANN | FIRE | REVIEW | Denied | Please provide a response letter. Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The hazard classification of the building, including any special hazards. 3. The density required for the hazard. |
| 03/25/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | A demand flow of 100 GPM through a 2" water meter results in an excessive pressure drop and a velocity greater than the maximum 8 FPS allowed for either plastic or copper piping. In addition, Tucson Water limits the 2" meter to a maximum demand of 80 GPM. Reference: Sections 610.2 and 610.12, UPC 2006. |
| 04/01/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/02/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/10/2008 | TERRY STEVENS | ZONING | REVIEW | Approved |