Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM00002
Parcel: 137055110

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T08CM00002
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2008 MICHAEL ST. PAUL ZONING REVIEW Needs Review
01/02/2008 MICHAEL ST. PAUL ZONING_QA REVIEW Needs Review
01/02/2008 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
01/02/2008 BIANCA RAMIREZ ENGINEERING_QA REVIEW Passed
01/02/2008 BIANCA RAMIREZ ENGINEERING REVIEW Needs Review
01/03/2008 DAVE MANN FIRE REVIEW Denied Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2008 DELMA ROBEY OUT TO CUSTOMER Completed