Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T08BU02190
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/23/2008 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 12/24/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:T08BU02190 695 E GRANT RD NEW FUEL TANKS AND DISPENSERS THESE PLAN DO NOT INCLUDE THE WIRING CONNECTING THE EQUIPMENT ( TANKS AND DISPENSERS,VEEDER ROOT SYSTEM) TO THE BUILDING. ALSO ANY OTHER WIRING ASSOSIATED WITH THE CONNECTION TO THE BUILDING SHOULD BE INCLUDED. THESE PLANS ARE REQUIRED TO BE SEALED BY AN ELECTRICAL ENGINEER PER THE COMMERCIAL SUBMITTAL REQUIREMENTS. RAY T MAJUTA ELECTRICAL PLAN CK DSD TUCSON, AZ 12-24-08 520-837-4988 |
| 12/30/2008 | DROBEY1 | FIRE | REVIEW | Needs Review |