Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08BU02188
Parcel: 11901065B

Address:
3301 S 6TH AV

Review Status: Completed

Review Details: TANKS

Permit Number - T08BU02188
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2009 DELMA ROBEY APPROVAL SHELF Completed
01/23/2009 DELMA ROBEY OUT TO CUSTOMER Completed
01/23/2009 DELMA ROBEY REJECT SHELF Completed