Permit Number: T08BU02188
Parcel: 11901065B

Address:
3301 S 6TH AV

Review Status: Completed

Review Details: TANKS

Permit Number - T08BU02188
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: New Fuel Tanks and Dispensers
3301 S 6TH ST
T08BU02188


The electrical plans have been denied for the following;

1. All sheets are to be stamped and dated, some sheets are not stamped.
2. Electrical engineer is to stamp electrical sheets.
3. Provide the Electrical Plans for the store showing the panel and loads for the tanks and dispensers.
4. Provide information on the Veeder Root System to be used.

Ray T Majuta
Elect Plan Ck
DSD Tucson
520-837-4988
1/11/09
12/23/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
12/23/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/24/2008 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2009 THAUSER1 REJECT SHELF Completed