Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2011 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 02/08/2011

Brown/Rita Ranch Lot 19 Grading Plan Comments:

1. Provide construction details (including cross section details, dimensions, slopes, materials, riprap size, filter fabric, etc.) for the proposed revisions (i.e. gravel transition, extruded curbs, thickened edge, etc.).
2. Show the revision symbol next to the proposed extruded curb and fence near the wash.
3. Clarify what is proposed outside the area labeled "end fence" along the northern, southern and western parcel lines.
4. Ensure that the proposed gates will be opened for trash collection service.
5. The line labeled "disturbed area" does not indicate if the disturbance is proposed east or west of the line. Clarify.
6. Will the extruded curb, along the eastern bank of the wash, have opening to accommodate drainage? Clarify and show the details on the plan.
7. Although the curb details, on Sheet 2/2, are labeled "extruded curb", the details are showing the standard vertical curb. Revise the details.
8. Revise General Note #17 to read as follows:

CALL FOR SWPPP INSPECTION AND PRE-CONSTRUCTION MEETINGS. FOR A PDSD ENGINEERING INSPECTIONS, CALL IVR (740-6970), OR SCHEDULE WITH A CUSTOMER SERVICE REPRESENTATIVE AT THE PLANNING AND DEVELOPMENT SERVICES DEPARTMENT, OR CONTACT DSD ENGINEERING AT 791-5550 EXTENSION 2101, OR SCHEDULE INSPECTIONS ONLINE AT: http://cms3.tucsonaz.gov/pdsd/inspections.

9. Revise in the, General Notes, all references to "Development Services Department" and "DSD" to "Planning and Development Services Department" and "PDSD".
10. Add a note or show in a typical detail that proposed cut or fill slopes shall be set back at least 2' from the parcel line.
11. Provide a detailed response letter with the next submittal that explains how the comments were addressed and references the exact locations/sheets where the revisions were made.

If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov
02/10/2011 MICHAEL ST. PAUL ZONING REVIEW Denied February 10, 2011

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T08BU02180 Revision of Grading Plans for D08-0038

Address:
8198 South Camino de Cafe

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. It appears that the revised grading plan matches the approved development plan. Please provide one copy each of the approved and stamped Development Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.
02/22/2011 CPIERCE1 NPPO REVIEW Needs Review