Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08BU02178
Parcel: 141113770

Review Status: Completed

Review Details: GRADING

Permit Number - T08BU02178
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2009 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 01/15/2009

Brown/Rita Ranch Lot 14 Grading Plan Comments:

1- Provide the "T08BU02178" number in the Tile Block.
2- Provide the administrative address.
3- Show the location of the basis of elevation.
4- Show the basis of bearing and the tie between the basis of baring and on corner of the subject parcel.
5- Provide construction details (including dimensions, slopes, materials, riprap size, filter fabric, etc.) for the trash enclosure and all proposed drainage and erosion control structures. Additionally, provide erosion control pads downstream of the proposed curb openings.
6- Add a note or show in a typical detail that proposed cut or fill slopes shall be set back at least 2' from the parcel line.
7- Wheelchair ramps shall be built in accordance with City of Tucson Standard Detail 207. Revise Keynote #2 accordingly.
8- Provide curb radii wherever applicable.
9- Provide a typical parking space detail including all dimensions.
10- Provide the widths of all proposed and existing sidewalks including pedestrian refuge areas adjacent to the building.
11- Keynote #6 callout, adjacent to the southern parking spaces appears to be incorrect.
12- Provide the dimension between the loading zone and the face of curb along the northern property line.
13- Add the following general notes:

a. The approved Grading Plan is the only acceptable construction plan onsite. The Contractor may not use any other plans, such as the approved Tentative Plat and/or Development Plan, for construction purposes. The Contractor may ask the Development Services Inspector to consult with the other approved plans for additional information or details that might not be included on the approved grading plan but needed for completion of work.
b. Add a note, which states that any engineering work to be done below grade (i.e. toe-downs, cutoff walls, drainage pipes/structures, etc.) shall not be back filled until Development Services Inspector inspects the work and approves it.
c. The contractor is not permitted to make an autonomous decision to carry out construction field changes without prior written approval from the Engineer of Record and the City of Tucson Development Services Department.
d. CALL FOR PRE-CONSTRUCTION MEETINGS. FOR A DSD ENGINEERING INSPECTIONS, CALL IVR (740-6970), OR SCHEDULE WITH A CUSTOMER SERVICE REPRESENTATIVE AT THE DEVELOPMENT SERVICES DEPARTMENT, OR CONTACT DSD ENGINEERING AT 791-5550 EXTENSION 2101, OR SCHEDULE INSPECTIONS ONLINE AT: http://WWW.CI.TUCSON.AZ.US/DSD/ONLINE_SERVICES/ONLINE_PERMITS/ONLINE_PERMITS.HTML.
e. The project will be in compliance with City of Tucson Development Standard 11-01.0 (Excavation and Grading).
f. A copy of the approved Grading Plan, Grading Permit, and any Geotechnical Reports shall be kept at the site at all times, until final grading approval.
g. Any revision to the Grading Plan MAY require a re-submittal of a revised grading plan for review. Contact DSD Engineering at 791-5550 to discuss changes in grading design.
h. If grading construction is expected to last longer than the expiration date of the grading permit, contact DSD to renew/extend the Grading Permit. If Final Grading Inspection has not been completed before the Grading Permit expires, and the permit has not been renewed, additional fees and reviews may be required.
i. Contact Permits and Codes at 791-5100 for any questions regarding any right-of-way permit requirements.
j. As-builts and letters of completion for the overall project are required.
k. The Engineer of Record shall submit a statement of conformance to as-built plan and the specifications.
l. The permitee shall notify the DSD when the grading operation is ready for final grading inspection. Final grading approval shall not be given until all work, including installation of all drainage facilities and their permanent protective devices, and all erosion control measures have been completed in accordance with the approved grading plan and grading permit, and any required reports have been submitted.

14- Work in the public right of way requires an excavation permit and/or may require a private improvement agreement. Check with City of Tucson Department of Transportation Permits and Codes for additional information.
15- Resubmit the redlined grading plan with future Grading Plan submittals for comparison.
16- Provide a detailed response letter with the next submittal that explains how the comments were addressed and references the exact locations/sheets where the revisions were made.
17- Additional information may be required with next submittal.

SWPPP Comments:

1. It is recommended that BMP's be used, on this project, to reduce the amount of pollutants that might exit this site and enter US waters. However, since the proposed area to be disturbed is less than one acre (0.89 acre), a SWPPP is not required for this project.
2. The reviewer conducted a courtesy review on the SWPPP and found the provided information in the Report is acceptable. The site map, however, needs to show additional information, such as the proposed BMP's and their locations, a stabilized entrance, storage and washout locations, etc.

If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov
12/22/2008 MICHAEL ST. PAUL ZONING REVIEW Denied December 22, 2008

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T08BU02178 Grading Plans for D08-0041?

Address:
8166 South Camino De Cafe

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. In addition, we could not verify that the grading plan was in compliance with a approved development plan for Zoning Review. At present, there is no development plan associated with this address. Please submit two copies of the approved and stamped Development Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.
12/30/2008 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved development plan including the landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance when the approved documents are included in the submittal. Ensure that all Engineering comments and concerns are addressed.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2009 THAUSER1 OUT TO CUSTOMER Completed
02/09/2009 SUE REEVES REJECT SHELF Completed