Permit Review Detail
Review Status: Active
Review Details: TANKS
Permit Number - T08BU02157
Review Name: TANKS
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 941 W Fairview Business Park PL Fuel tank Installation T08BU02157 Electrical has been rejected for the following; 1. City of Tucson Development Services Department, Commercial Submittal Requirements, states, "A licensed electrical engineer is required when electrical designs exceed 400 amps or involve hazardous locations," This being a hazardous location, electrical work to be sealed by an EE. Some of the sheets are not sealed at all. 2.Provide a copy of electrical sheets for permit # T08CM00804, which includes the panel provided for the circuits supplying power to the dispensers and the pumps. 3. Panel FP is required to have load calculations in place for dispensers and pumps. 4. Wish to review electrical plans for permit # T08CM00804 to check info on Veeder Root System. Ray T Majuta Electrical Plan Check City Of Tucson, DSD 520-837-4988 1/07/09 |
| 12/15/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/17/2008 | DAVID RIVERA | ZONING | REVIEW | Denied | Zoning cannot approve the pklans at this time. Submit two copies of the approved and stamped site plan/landscape plans with teh next submittal. Zoning can review the plan over the counter with an appointment. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/09/2009 | SUE REEVES | REJECT SHELF | RECEIVED |