Permit Number: T08BU02004
Parcel: 11917013H

Address:
3502 S 6TH AV

Review Status: Completed

Review Details: REVISION - GRADING

Permit Number - T08BU02004
Review Name: REVISION - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2011 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Veterans Plaza
T08BU02004
Grading Plan (Revision)

TRANSMITTAL DATE: April 5, 2011

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved development plan. Please submit two copies of the approved, stamped development, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Steve Shields,
(520) 837-4956

C:\planning\grading\t07bu01474.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Grading plan and approved development plan and additional requested documents
04/11/2011 LOREN MAKUS ENGINEERING REVIEW Denied April 14, 2011
T07CM01474/T08BU02004

1. The conclusions of the Hydrologic/Hydraulic Report (JAS Engineering, Jeffrey A Stanley, 4-4-11) are accepted.
2. As we have previously discussed, show how the water harvesting basins will be constructed. Provide dimensions on the sections showing the water harvesting areas. The change in grade and labeled slopes seem to result in the available space being used up by slopes and setbacks.
3. Also provide a section along the length of the water harvesting basins along the street frontage to demonstrate that effective water harvesting will be achieved along the whole length of the basins.
4. The sections are labeled with scale notations of ¾" = 1'. The scale doesn't match the drawings. Please provide correct notations.
5. The section callouts on sheet G-01R don't refer to the correct sheets for the details. Provide correct sheet references. Make sure there are callouts for all provided details and make sure the details reflect what is on the plan view.
04/18/2011 ANDREW CONNOR NPPO REVIEW Denied Ensure that all Engineering comments and concerns are addressed prior to Landscape / NPP approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2011 DELMA ROBEY OUT TO CUSTOMER Completed
04/20/2011 SUE REEVES REJECT SHELF Completed