Review Details: GRADING

Permit Number - T08BU01684
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2008 DAVID RIVERA ZONING REVIEW Denied 09/19/2008

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan on this review.

2. Zoning could not verify that the grading plan was in compliance with the DSD stamped and approved, preliminary, or unapproved site plan. Please submit two copies of the approved and stamped site plan, landscape, and NPPO plans with the next grading plan submittal.

3. Please ensure that the grading plan matches the DSD approved and stamped site plan.

4. Zoning will re-review the grading plan on the next submittal to ensure compliance with the DSD approved and stamped site plan. Additional comments may be forthcoming.
09/30/2008 ANDREW CONNOR NPPO REVIEW Denied Site plan approval is necessary to continue review.
10/10/2008 LOREN MAKUS ENGINEERING REVIEW Denied October 14, 2008
T08BU01684
Bellevue Apartments Grading Plan
Reviewed by: Loren Makus, EIT

The grading plan cannot be approved as submitted. The grading plan cannot be approved until the site plans have been approved.

Show representative spot elevations throughout the site. Especially indicate the elevations of the tops of the water harvesting areas.
Demonstrate with elevations, details and notes that the water harvesting areas will collect water along their whole length. Show intermediate berms or other mechanisms for maximizing the effective capacities of the basins.
Provide estimated cut and fill quantities on the grading plan.
Provide a detail or revise the plan view of the solid waste enclosure showing the required elements and dimensions. Include bollards along the side walls of the enclosure. Provide dimensions showing 10 feet of clearance between the bollards as well as between the rear wall bollards and the gate.
Provide representative existing and proposed spot elevations and cross sections showing existing and proposed grades to establish that the project will be in compliance with the differential grading requirements of the grading development standard.
Include the approved landscape plan with the grading plan so the effective integration of water harvesting and landscaping can be demonstrated.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/17/2008 THAUSER1 OUT TO CUSTOMER Completed
10/17/2008 SUE REEVES REJECT SHELF Completed