Permit Number: T08BU00919
Parcel: 99999999A

Address:
9955 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T08BU00919
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2009 MICHAEL ST. PAUL ZONING REVIEW Denied January 14, 2009

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T08BU00919 Grading Plans for S06-208

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. The Grading Plan submitted appears to match the Tentative Plat for Red Colt Ranch (RCP). Provide the correct activity number (T08BU00919) on the grading. It is also helpful if you provide the subdivision plat number (S06-208) on the grading plans.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming.
01/15/2009 ANDREW CONNOR NPPO REVIEW Approv-Cond Provide the correct activity number (T08BU00919) on the grading plan. Approval stamp pending upon re-submittal.
01/30/2009 LOREN MAKUS ENGINEERING REVIEW Denied February 3, 2009
T08BU00919
Red Colt Ranch Grading Plan

The grading permit cannot be approved as submitted. Please revise the Grading Plan and SWPPP. Include a response letter that completely describes the revisions made to address each comment.

1. Ok
2. Ok
3. The rezoning conditions include a requirement for a sediment trap for the inlet to the basin. Show details for the sediment trap that meet the requirements of the rezoning conditions. Revise the drainage report and grading plan to demonstrate that the sediment trap design standards in the detention/retention manual section 3.4.2 on pages 51 through 53.
4. OK
5. Provide construction information for the concrete slab including slab thickness. Indicate that a bench will be installed in accordance with the tentative plat.
6. OK.
7. OK.
8. Ok.

SWPPP
9. The SWPPP will be approved when the Grading Plan is approved..

If you have any questions or wish to set up a meeting I can be contacted at loren.makus@tucsonaz.gov

Loren Makus
Senior Engineering Associate

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2009 DELMA ROBEY OUT TO CUSTOMER Completed
02/05/2009 SUE REEVES REJECT SHELF Completed