Permit Review Detail
Review Status: Completed
Review Details: WALLS SUBMITTAL
Permit Number - T08BU00839
Review Name: WALLS SUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET SP-2; SECTION D: 5'-0" +/- VERTICAL DIMENSION REFERS TO SHEET X-X. CLARIFY. 2. SHEET SP-2; SECTION D: CLARIFY 8" CMU PIER REINFORCING NOTE (4-#5 VERT. EA. WAY?). IDENTIFY TOP BARS IN WALL. 3. CALCULATIONS: PROVIDE CALCULATIONS FOR METAL FENCE ABOVE CMU AND FOOTING AT THAT LOCATION. 4. SHEET SP-2; SECTION E: SUBMIT FORMS FOR SPECIAL INSPECTIONS FOR 1) THE WELDING OF REINFORCEMENT, AND 2) FIELD WELDING. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/13/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 05/13/2008 | SHANAE POWELL | REJECT SHELF | Completed |