Permit Number - T08BU00502
Review Name: GRADING
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2008 | ANY | NPPO | REVIEW | Active | |
| 03/14/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Sun Tran Bus Storage & Maintenance Facility T08BU00502 Grading Plan (1st Review) TRANSMITTAL DATE: March 14, 2008 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections. 3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t08bu00502 RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents |
| 04/09/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Submit a complete grading plan submittal, including a plan labeled "Grading Plan," a SWPPP prepared in accordance with the current general permit and other supporting documentation. |