Permit Number: T08BU00374
Parcel: 13329001A

Review Status: Completed

Review Details: REVISION - GRADING

Permit Number - T08BU00374
Review Name: REVISION - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2009 PAUL MACHADO ENGINEERING REVIEW Denied To: Ken Perry, P.E. DATE: October 14, 2009
4625 E. Fort Lowell Road.
1745 E. River Road, Suite 101
Tucson, Arizona 85712
SUBJECT: Sahuaro High School, 545 N. Camino Seco Road
Grading Plan "As-Builts" T08BU00374(1st Review)
T14S, R15E, Section 09

RESUBMITTAL REQUIRED: Grading Plan "as-builts" and Drainage Report.

The closure documentation / as-built package including the Grading Plan "as-builts" (GP) and Drainage Report (DR) cannot be approved as submitted. A field visit was performed on October 2, 2009. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP "as-builts".
2. Show details of the 10" corrugated HDPE pipe for the roof drain stormwater and of the rip-rap splash pad including post barricades for protection from vehicles. The GP indicates that the HDPE pipe day lights at the edge of the concrete sidewalk, not in the middle of the "maneuvering area", which that location of the splash pad is not recommended. Perhaps extending the pipe and moving the splash pad further south may alleviate this problem.
3. There is evidence of stormwater pollution (silt) onto the existing tennis courts south of the gym and ultimately will reach the wash. This area (dirt area) south of the new gym shall be stabilized to minimize the stormwater pollution potentially going into the wash.
4. Delineate 100-year W.S.E.L., Floodplain and erosion hazard setback.
5. Call out peak discharges entering and exiting the site.
6. List the City of Tucson Site plan (T08CM00039) and Flood Plain Use permit (T08OT01614) activity number on each sheet.

Drainage report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. This site is affected by the City of Tucson flood Hazard areas and is subject to Chapter 29 of the City of Tucson flood plain ordinance.
3. A Drainage report is required for parcels affected by 100 year flows of 100 cfs, of more per S.M.D.D.F.M., chap. II, 2.1.2, therefore the drainage study report is not acceptable. The DR must be submitted along with the as-built package re-submittal.
4. The content and format of the DR should follow S.M.D.D.F.M., chap. II, 2.1.3.
5. Show the project address on the cover of the DR.
6. Address the wash crossing at the access road in the DR. This includes but is not limited to:
" Encroachment analysis.
" Amount of conveyance of the RCPE's.
" All weather access, if applicable, for Vicksburg Street adjacent to the wash crossing ("as-built" back water depth).
" Delineate 100-year W.S.E.L., Floodplain and erosion hazard setback.
" Recommended pavement section from a revised Geotechnical reports.
7. List the City of Tucson GP activity number (T08BU00374) on the cover sheet.
8. Provide fence ht. recommendations (flow thru openings) at the south and west property lines intersecting the wash.
9. Show details of the 10" corrugated HDPE pipe for the roof drain stormwater and of the rip-rap splash pad including post barricades for protection from vehicles. The GP indicates that the HDPE pipe day lights at the edge of the concrete sidewalk, not in the middle of the "maneuvering area", which the location of the splash pad is not recommended. Perhaps extending the pipe and moving the splash pad further south may alleviate this problem.
10. "As-built" data shall be used in all new calculations.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:\545 N. Camino Seco_Grad 2

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2010 CPIERCE1 OUT TO CUSTOMER Completed