Permit Number: T08BU00244
Parcel: 13305054L

Review Status: Completed

Review Details: GRADING

Permit Number - T08BU00244
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2008 JOE LINVILLE NPPO REVIEW Denied Revise the grading plans to correspond with the revised site plans as necessary. LUC 1.1.3
Approval of the grading plan can occur when the site plan is determined to be in accordance with the COT Land Use Code.
02/15/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Calvary Chapel of Tucson - Parking Expansion
T08BU00244
Grading Plan (1st Review)

TRANSMITTAL DATE: February 15, 2008

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could approve the grading plan until the site plan is approved. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07bu00244

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents
02/15/2008 MATT FLICK ENGINEERING REVIEW Denied The grading plan is not approved, the following comments are offered:

1. Permits & Codes' phone number is 791-5100 (Grading & Paving Note #27).

2. Show existing bus stop location on Sheet C.5.

3. Show proposed transit improvements per the approved Speedway - Camino Seco to Houghton Road plans. Locate the proposed driveway out of the proposed transit improvements.

4. Near side SVT length is 345' per the Development Standards.

5. Show existing and proposed SVTs.

6. Max. driveway width = 35' per the Tucson Access Management Guidelines (TAMG). Max. width = 30' at property line per TAMG.

The drainage report is not approved. Provide the percolation testing and infiltration calculation(s) to show the retention basin(s) will drain within 12 hours.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2008 DELMA ROBEY OUT TO CUSTOMER Completed
03/19/2008 SUE REEVES REJECT SHELF Completed