Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T08BU00244
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2008 | JOE LINVILLE | NPPO | REVIEW | Denied | Revise the grading plans to correspond with the revised site plans as necessary. LUC 1.1.3 Approval of the grading plan can occur when the site plan is determined to be in accordance with the COT Land Use Code. |
| 02/15/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Calvary Chapel of Tucson - Parking Expansion T08BU00244 Grading Plan (1st Review) TRANSMITTAL DATE: February 15, 2008 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could approve the grading plan until the site plan is approved. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal. 3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t07bu00244 RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents |
| 02/15/2008 | MATT FLICK | ENGINEERING | REVIEW | Denied | The grading plan is not approved, the following comments are offered: 1. Permits & Codes' phone number is 791-5100 (Grading & Paving Note #27). 2. Show existing bus stop location on Sheet C.5. 3. Show proposed transit improvements per the approved Speedway - Camino Seco to Houghton Road plans. Locate the proposed driveway out of the proposed transit improvements. 4. Near side SVT length is 345' per the Development Standards. 5. Show existing and proposed SVTs. 6. Max. driveway width = 35' per the Tucson Access Management Guidelines (TAMG). Max. width = 30' at property line per TAMG. The drainage report is not approved. Provide the percolation testing and infiltration calculation(s) to show the retention basin(s) will drain within 12 hours. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/19/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 03/19/2008 | SUE REEVES | REJECT SHELF | Completed |