Permit Number: T08BU00022
Parcel: 99999999A

Address:
8525 E 22ND ST

Review Status: Completed

Review Details: GRADING

Permit Number - T08BU00022
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2008 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved tentative plat including landscape and native plant preservation plans for reference. The grading application will be reviewed for compliance when the approved documents are included in the submittal.
08/18/2008 STEVE SHIELDS ZONING REVIEW Denied August 18, 2008

Development Services Department

Steve Shields
Lead Planner

T08BU00022 Grading Plans for S06-221

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved tentative plat. Please submit one copy of the CDRC approved and stamped tentative plat, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming.
09/04/2008 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and floodplain Review, 09/04/2008

Barrio Arroyo Grading Plan Comments:

1- Provide a copy of the approved and stamped Tentative Plat. Please be advised that the grading plan shall be approved only after the tentative plat is approved.
2- The barricading at Basin "R" ramp entrance shall have a gate for access.
3- Provide, on the Grading Plan, the approved DSMR number for the proposed eastern entrance closure.
4- Work in the public right of way and within Palm Tree Drive Wash requires an excavation permit and/or a private improvement agreement. Check with City of Tucson Department of Transportation Permits and Codes for additional information.
5- The proposed drainage structures within Palm Tree Drive Wash require a private drainage easement from the City to allow the private maintenance of the the structures. Check with City of Tucson Department of Transportation Permits and Codes for additional information.
6- The detention basin spillway into Palm Tree Drive Wash requires toe downs on the sides similar to the toe down at the bottom end. Revise the applicable details accordingly. This is also a Permits and Codes requirement.
7- Resubmit the redlined plan with future Grading Plan submittals.
8- Provide a detailed response letter with the next submittal that explains how the comments were addressed and references the exact locations/sheets where the revisions were made.

SWPPP Comments:

The SWPPP is acceptable; however it can not be approved until the Grading Plan is approved. Additional SWPPP related information may be required if the Grading Plan is significantly modified.

If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2008 CPIERCE1 OUT TO CUSTOMER Completed
09/09/2008 SUE REEVES REJECT SHELF Completed