Permit Number: T07PL01397
Parcel: 117021250

Review Status: Completed

Review Details: PLUMBING

Permit Number - T07PL01397
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. According to the contractor, TracPipe, not carbon steel pipe, will be used for the gas piping. Resolve this issue with the contractor and coordinate the drawings and specifications as required. If TracPipe will be used, provide the sizing calculations.
2. Show the sizes of the required combustion/relief openings for the water heaters in the attic.
3. Provide a schedule of the fixtures being replaced.