| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. According to the contractor, TracPipe, not carbon steel pipe, will be used for the gas piping. Resolve this issue with the contractor and coordinate the drawings and specifications as required. If TracPipe will be used, provide the sizing calculations. 2. Show the sizes of the required combustion/relief openings for the water heaters in the attic. 3. Provide a schedule of the fixtures being replaced. |