Plan Number: T07PI00039
Parcel: Unknown

Address:
6702 S WILMOT RD

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T07PI00039
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2008 JOSE ORTIZ DOT TRAFFIC REVIEW Denied January 3, 2008
ACTIVITY NUMBER: T07PI00039
PROJECT NAME: Little Town & Wilmot Industrial Park
PROJECT ADDRESS: 6702 S Wilmot Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

3. Install R1-1 (Stop Sign) with street names at the proposed roadway entering this development off of Wilmot Road per PCDOT & TDOT Signing Manual (2002) Chap 5-11, 5-12, and Chap 9-2.

4. Install R2-1 (25MPH Speed Limit Sign) at the proposed roadway entering this development off of Wilmot Road per PCDOT & TDOT Signing Manual (2002) Chap 9-10.

5. Parking is not allowed in cul-de-sacs from PRC to PRC. So indicate on the plans by showing no parking signs on the plans. (DS 3-01.0 fig 20) (straight cul-de-sac)

6. Sheet 2 of 9, Revise the general signing note #1 to reflect the current MUTCD edition (2003 Edition).

7. Provide a detail of the No Parking sign to be used. If needed refer to the attached drawing provided with the Traffic Engineering red line drawings.

8. Place the PIA and CDRC Case number on the cover sheet.



If you have any questions, I can be reached at 791-4259 x 76730 or Jose.Ortiz@tucsonaz.gov
01/04/2008 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED Completed
01/04/2008 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed
12/03/2007 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/03/2007 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/03/2007 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/03/2007 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/03/2007 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/03/2007 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/03/2007 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/03/2007 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/03/2007 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
12/27/2007 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed this plan and have the following comments:

1. Please provide a Streets and Traffic Maintenace signature block.
2. Boundary survey info needs to be stamped by a registered land surveyor.
3. Who will be responcible for the maintnenace of the concrete drainage channel and the basins?
4. You need to call out saw cutting the existing pavement on Wilmot where your project will tie in.
5. Will any landscaping installed be maintained by the Home Owners Association?
6. Contour elevations would be helpful on the drainage basin detail sheet.

No further comments.
12/28/2007 RICHARD LEIGH DOT ENGINEERING REVIEW Completed A PIA is not required, Streets are private.
12/28/2007 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. Please submit a copy of your approved NPPO plan. Looking to see if the areas within the ROW have included and will there be any Native Plant impacts.
2. It appears that you have at least two common areas. If they will be landscaped with irrigation, please submit plans. NOTE: you can not place private irrigation lines under public roadways without a legal easement.