Plan Number: T07PI00037
Parcel: Unknown

Address:
7150 E 22ND ST

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T07PI00037
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2008 Blanca Espino DOT ENGINEERING REVIEW Approv-Cond PIA Plan
1. Please include a detail letter of explanation with the next submittal indicating where and how revisions were made. Single word responses are unacceptable. Include plans/redlines from previous plan submittal.

2. Sheet 2, Indicate the Docket & Page recording for the "New 15' Water Easement."

3. Sheet 3, Indicate the Docket & Page recording for the "Pedestrian Access Easement."

4. This comment was not addressed - Sheet 3, Call out the New Right of way as per RES-2007-011. Indicate the Existing Right of way.

5. Sheet 4, Detail 4 does not reflect the side slope information as noted on Sheet 2. Hinge points of cut and fill slopes must have a minimum setback of two feet from right-of-way.

6. Handicap ramp located at 22nd & Kolb must be in compliance with A.D.A. guidelines. Indicate a callout note.
05/28/2008 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
05/28/2008 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed