Plan Number: T07PI00037
Parcel: Unknown

Address:
7150 E 22ND ST

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T07PI00037
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2008 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Completed
02/07/2008 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
02/07/2008 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
02/07/2008 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
02/07/2008 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
02/07/2008 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Completed
02/07/2008 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
02/07/2008 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Passed
02/07/2008 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Passed
02/22/2008 GARY WITTWER DOT LANDSCAPE REVIEW Approved
02/29/2008 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
03/03/2008 Blanca Espino DOT ENGINEERING REVIEW Denied PIA Plan
1. Please include a detail letter of explanation with the next submittal indicating where and how revisions were made. Single word responses are unacceptable. Include plans/redlines from previous plan submittal.

2. Floodplain Use Permit T07OT01752 does not indicate construction for right-of-way improvements. Correct FUP with DSD to indicate work in the public right-of-way.

3. Indicate Saw-cut area with a hatch or shaded symbol. See redlines.

4. Sheet 2, Indicate the Docket & Page recording for the "New 15' Water Easement."

5. Sheet 3, Indicate the Docket & Page recording for the "Pedestrian Access Easement."

6. This comment was not addressed - Sheet 3, Call out the New Right of way as per RES-2007-011. Remove verbiage, "Existing Right of way."

7. Sheet 4, Detail 4 does not reflect the side slope information as noted on Sheet 2. Hinge points of cut and fill slopes must have a minimum setback of two feet from right-of-way.

8. Handicap ramp located at 22nd & Kolb must be in compliance with A.D.A. guidelines. Indicate a dimensioned detail for all improvements. Truncated Domes required.

9. Construction Note #5 does not coincide with Detail 4 of Sheet 4. Indicate the correct Standard Detail.

10. Remove Sheets S1.0 - S2.1
03/07/2008 JOSE ORTIZ DOT TRAFFIC REVIEW Approved
03/10/2008 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
03/10/2008 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed