Plan Number: T07PI00035
Parcel: Unknown

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T07PI00035
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2007 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/01/2007 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/01/2007 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/01/2007 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/01/2007 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/01/2007 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/01/2007 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/01/2007 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/01/2007 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
11/19/2007 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed this plan and have the following comments:

1. Will there be any landscaping installed with this prject? If so, please submit the landscape plan to Paul Rosenboom at 4004 S. Park Avenue Bld #2 for review.
2. All work in the right of way needs to be coordinated with Paul Rosenboom at 791-5279 ext 234.
3. Sheet 5 - Detail B - Is there anything planned to keep the motoring public from using the 12' asphalt path?
12/04/2007 GARY WITTWER DOT LANDSCAPE REVIEW Denied Please address the Native Plant Preservation Ordinance. This is a Gateway Route.
12/05/2007 JOSE ORTIZ DOT TRAFFIC REVIEW Approv-Cond Place the PIA and CDRC Case number on the cover sheet.
12/07/2007 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED Completed
12/07/2007 Blanca Espino DOT ENGINEERING REVIEW Denied PIA Plan
1. Please include a detail letter of explanation with the next submittal indicating where and how revisions were made. Single word responses are unacceptable. Include plans/redlines from previous plan submittal.

2. In title block, add assigned I-Plan Number, I-2007-046 to all sheets.

3. Indicate assigned DSD activity number T07PI00035 above title block. See redlines.

4. Indicate the following Paving Notes:

q Pavement Section Design documentation, are in accordance to the approved Geotechnical Report, Report Name and Firm Name, Project Number.

q The City shall not be held liable for any errors and/or omissions on these plans. Items not meeting City Standards shall be repaired/replaced at no cost to the City.




q Contractor shall call Blue Stake as mandated by the Arizona Revised Statutes at 1-800-782-5348 before any construction begins to verify location of existing utilities shown or not shown. Existing utility locations shown hereon are only approximate. It is the contractor's responsibility to confirm horizontal and vertical location of all utilities without damaging same. Damaged utilities shall be repaired at no expense to the City.

q Upon commencement of work, traffic control devices shall be posted and maintained by the contractor until such time as the work is completed. All warning signs barricades etc. shall be in accordance with the manual on uniform traffic control devices adopted by the State of Arizona pursuant to A.R.S. 28-065. Contact Traffic Engineering, 791-4259, 48-hours prior to placing or removing any said traffic control devices.

5. All Rezoning requirements pertaining to the rights-of-way must be met. Approved Development Plan D06-003, Rezoning Condition #4 indicates a "Left turn lane and appropriate tapers shall be provided to serve the vehicular access point on Old Spanish Trail." Graphically indicate detail on Sheet 2 & 3.

6. Sheet 2 & 3, Indicate percent slope in profile.

7. Sheet 2 & 3; A 6 inch vertical curb or an 8 foot wide space is required along road to act as a barrier between road and pedestrians. Correct and revise.

8. Sheet 5, Details A, B, & C; Hinge points of cut and fill slopes must have a minimum setback of two feet from right-of-way. (Slope on private side). D.S. 11-01.9.0 (9.2, 9.3 & Figure 2)

9. Sheet 5, Pedestrian areas/shoulders along side of strip paved/thickened edge streets should be a minimum of 8 feet wide, slope @ 2% and be separate to drainage ditches/channels.

10. See redlines for additional corrections.
12/07/2007 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed