Plan Number: T07PI00031
Parcel: Unknown

Address:
9941 E 22ND ST

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T07PI00031
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2009 RICHARD LEIGH DOT ENGINEERING REVIEW Denied November 19, 2009

PROJECT: Red Colt Ranch, Bonanza Ave., 22nd St and Red Colt Road, PIA Plan T07PI0007

PROJECT REVIEWER: Richard Leigh, Senior Engineering Associate Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. Submit Geotechnical Report supporting the proposed pavement structural section for Red Colt Road. The drainage report submitted does not address the pavement design.

2. Sheet 5: Indicate the placement of a vertical curb (6" reveal) at back of ramp on Curb Access Ramp detail.

3. Sheet 2: Clarify how the existing pavement edge will transition into the proposed curb on 22nd Street. Provide stationing of the start of the transition.

4. Sheet 5: Provide a standard curb knuckle per Development Standard 3-01.6.2.C. 1.F. The back of wedge should be parallel to the property line along the curb knuckle on Red Colt Road.

5. Show and label all existing utility infrastructure (poles, cabinets pull boxes, etc.) within the public right-of-way and indicate as to their disposition if encroaching. There are existing power poles and utility cabinets along the 22nd street that are not shown in the plan view.

6. Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsoz.gov
11/30/2009 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
11/30/2009 JOSE ORTIZ DOT TRAFFIC REVIEW Denied
11/30/2009 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed