Plan Number: T07PI00025
Parcel: Unknown

Address:
9047 S RITA RD

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T07PI00025
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2007 ASHOFFS1 UTILITY CLEARANCES COT STREETS DIVISION Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
07/20/2007 ASHOFFS1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
07/20/2007 ASHOFFS1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
07/20/2007 ASHOFFS1 UTILITY CLEARANCES QUEST COMMUNICATION Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
07/20/2007 ASHOFFS1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
07/20/2007 ASHOFFS1 UTILITY CLEARANCES COX COMMUNICATION Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
07/20/2007 ASHOFFS1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
07/20/2007 ASHOFFS1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
07/20/2007 ASHOFFS1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied Please submit Utility Clearance Letters. You can find the form on-line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/UTLAWAREMEM__revised_062007_.pdf
08/07/2007 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. Please address the Native Plant Preservation Ordinance.
2. Please submit all landscape and irrigation plans for the ROW.
08/14/2007 RICHARD LEIGH DOT ENGINEERING REVIEW Denied August 13th, 2007

TO: DSD PIA Coordinator

SUBJECT: Rita 244, Offsite, PIA Plan T07PI00025

PROJECT REVIEWER: Richard Leigh, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommed approval of the PIA Plan at this time. THe following comments need to be addressed in the next submittal.

1. Include the plan number "I-2007-032" in title blocks.

2. Change title to include "Rita Road" in it.

3. Include the Development Services activity number "T07PI00025" on cover sheet.

4. Submit a copy of a geotechnical engineering report supporting the propesed pavement structural section with next submittal.

5. Verify that all shading and line work used in plan set are included in teh legend.

6. Provide a dinmensioned detail of each type of proposed curb access ramp in plan set. Additionally, indicate the use of truncated domes as the detectable warning device.

7. Label and station all ECRs, BCRs and radii of the proposed median island headers.

8. Indicate a thickened edge for new edge of pavement. Aditionally, provide a thickened edge detail.

9. Trenches within the pavement area that are wider than foru (4) feet wide require that the whole effected lane to be repaved (D.S. 3-03.3.3.B2).

10. Correct cross section callouts in the plan views.

11. Provide curb terminations per PC/COT Std. Dtl. 212 at the terminations of vertical curbing.

12. Align curb access ramps so that they are across from each other.

13. Sheet 7, Detail B: Indicate five (5) foot wide sidewalk and provide a cross section of the channel adjoining the sidewalk scuppers.

Sheet 7, Detail C: Provide the structural details of the sidewalk scupper.

15. Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or at Richard.Leigh@tucsonaz.gov
08/15/2007 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed this plan and have the following comments:

1. On the plan, roadway sections refer to a detail A/6 and should be A/7.
2. Sheets 4,5,6 - The plan shows curb access ramps. I believe that these are new ramps and will need to call out the use of truncated domes.
3 Sheet 4 - Box Culvert - What is the proposed erosion control at the outlet of the box culvert?
4. Sheet 5 Box Culvert - What is the proposed erosion control at the outlet of this box culvert?
5. Will there be any landscaping installed on this project? If so, please submit the landscaping and irrigation plan to Paul Rosenboom at 4004 S. Park Avenue, Bld #2 for review.
6. All work in the right of way needs to be coordinated with Paul Rosenboom at 791-3154 ext 234 to prevent damage to existing landscaping and irrigation.
7. Be advised that Rita Road is in bad shape and the pavement removal quantities may increas substancially to find sound pavement.

No further comments
08/20/2007 JOSE ORTIZ DOT TRAFFIC REVIEW Denied August 20, 2007
ACTIVITY NUMBER: T07PI00025
PROJECT NAME: Target Fulfillment Center
PROJECT ADDRESS: 9047 S Rita Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

3. Call out the radius to proposed curb returns along Rita Road. Any curb returns that have a radius larger then 25' will need a separate exhibit, such as auto-turn, illustrating what radius is recommended.

4. Provide an end median signage treatment per PCDOT & TDOT Signing Manual (2002) Chap 9-4A & 9-4B.

5. Re-stripe the median end/gore transition per PCDOT & TDOT Pavement Marking Design Manual (2002) Chapter 5-13. If possible, match the existing striping taper and location of the gore transition.

6. Install R1-1 (Stop Sign) with street names at the proposed roadway entering this development off of Rita Road per PCDOT & TDOT Signing Manual (2002) Chap 5-11, 5-12, and Chap 9-2. The intersection with the traffic signal will not require stop signs.

7. Provide a 'RIGHT LANE' (R3-5F) supplemental plaque under all new (R3-5R).

8. Provide Traffic Signal plans for review with the next submittal.

9. Place the PIA and CDRC Case number on the cover sheet.

10. Add the following Signing General Notes 5(a) & 5(b) per PCDOT & TDOT Signing Manual (2002) (Chapter 1, Sheet 12) to the Plans.

11. Add the following Pavement Marking/Striping General Notes to the Plans:

'ALL STREET STRIPING & SIGNAGE TO BE COORDINATED WITH C.O.T. TRAFFIC ENGINEERING CALL 791-4259 A MINIMUM OF 48 HOURS PRIOR TO THE INSTALLATION OR REMOVAL OF ANY SIGNAGE OR STRIPING. ALL REQUIRED STRIPING AND SIGNAGE WILL BE INSTALLED AT THE CONTRACTOR'S EXPENSE. NEW STRIPING TO BE THERMOPLASTIC MATERIAL. USE 2" SQUARE-TUBE POST AND SQUARE TUBE POST FOUNDATIONS FOR SIGNING. BARRICADE PLAN MUST BE SUBMITTED TO THE CITY OF TUCSON TRAFFIC ENGINEERING FOR APPROVAL 48 HOURS IN ADVANCE OF ANY WORK IN PUBLIC RIGHT OF WAY.'

'ALL NON-SIGNALIZED INTERSECTION STREET NAMES MUST HAVE E-W BLOCK NUMBER ADDRESSES FOR E-W ROADWAYS AND N-S BLOCK NUMBER ADDRESSES FOR N-S ROADWAYS.'

'THE CITY SHALL NOT BE LIABLE FOR ANY ERRORS AND/OR OMISSIONS ON THESE PLANS. ITEMS NOT MEETING CITY STANDARDS SHALL BE REPAIRED/REPLACED BY THE DEVELOPER/CONTRACTOR AND AT NO COST TO THE CITY.'

'ALL WARNING SIGN PANELS SHALL BE FLUORESCENT YELLOW DIAMOND-GRADE (DG-CUBED OR EQUIVALENT) SHEETING. ALL SCHOOL ZONE SIGNS SHALL BE FLUORESCENT YELLOW-GREEN DIAMOND GRADE (DG-CUBED OR EQUIVALENT) SHEETING. ALL OTHER SIGN PANELS SHALL HAVE HIGH INTENSITY PRISMATIC TYPE IV SHEETING.'



If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
08/21/2007 LHENDRI1 PIA COORDINATOR CUSTOMER CALLED Completed
08/21/2007 LHENDRI1 PIA COORDINATOR OUT TO CUSTOMER Completed