Permit Number: T07OT02591
Parcel: 13109235A

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T07OT02591
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2007 LOREN MAKUS ENGINEERING REVIEW Approved November 15, 2007

The applicant is authorized to use a portion of the flood hazard area (COT Flood Hazard Area) in the City of Tucson, Arizona, on the property described as 1841 South Craycroft Road for the purpose of installing lighting on a commercial lot.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations require the issuance of an additional Floodplain Use Permit.

The following conditions shall apply to this permit.

1. All work shall conform to the approved improvement plans which are made part of this permit (T07CM04007) which is for improvements in an existing structure.

2. No new structure as defined by the floodplain regulations is to be constructed.

3. All electrical connections shall be at least 2 feet above adjacent grade.

4. Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

5. Any additional improvements not reflected in the current permit will be subject to separate review and additional permits.

6. This permit becomes invalid and is subject to additional floodplain review, if any required improvement permit(s') changes the configuration of the structure and or site development.

This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Section.

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.