Permit Number: T07OT02452
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T07OT02452
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2007 LAITH ALSHAMI ENGINEERING REVIEW Approved November 19, 2007
FLOODPLAIN USE PERMIT NO. T07OT02452
ADDRESS: 350 N Wilmot
PROPERTY OWNER'S NAME: Carandolet Health Network

The applicant is authorized to use a portion of the Alamo Wash flood hazard area within Wilmot Road public right of way as shown on the attached plan and it includes the installation of the following:

1. A second left turn lane on the southbound leg.
2. Anew right turn lane, left turn lane realignment with a new GORE area, and a bus bay on the northbound leg.
3. A Pedestrian refuge and crosswalk constructed in the median.
4. Signal relocation, Re striping
5. Modification of North and South legs medians.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following conditions shall apply to this permit.

1. All work shall conform to the attached plans, which are made part of this permit.
2. The existing drainage patterns, within the impacted area, shall not be obstructed other what is shown on the attached plan.
3. Within 5 (five) days of issuance of this permit, through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "Construction proceeding under requirements of City of Tucson Floodplain Use Permit No. T07OT02452. For information please call 791-5550."
4. Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
5. This permit becomes invalid and is subject to additional floodplain review, if any required development permit (s) changes the configuration of the structure and or site development.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions set forth in this permit are not complied with. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Section.

(EXPIRATION DATE) Month: 11 Day: 19 Year: 2008

APPLICANT NAME: Kent Delph, P.E., Grenier Engineering.
ADDRESS: 1660 N. Alvernon Way, Tucson, AZ 85712
PHONE NO.: (520) 326-7082

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2013 CPIERCE1 OUT TO CUSTOMER Completed