Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07OT01360
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please incorporate the panel schedule onto the plans in accordance with the submittal requirements for the City of Tucson. 2) Please revise the denoted occupancy type and occupant load in accordance with chapter 6 and table 1004.1.1 of the 2006 IBC (F1 occupancy and 12 occupants). 3) Please revise the denoted plumbing code to the 2006 UPC as adopted by the City of Tucson. 4) Please provide additional information regarding the propane piping system in order to verify compliance with the 2006 UPC (i.e. total developed length, piping materials, supports, system pressure, etc.). 5) Please revise the denoted electrical code to the 2005 NEC as adopted by the City of Tucson. 6) Please revise the note regarding the combustion air louvers to have one within 12" of the ceiling/roof per section 103.2.3 of the 2006 UPC. 7) Please provide information regarding the roasting equipment in order to verify compliance with the manufacturer's installation requirements in accordance with section 106.3.1 of the 2006 IMC (i.e. hood requirements, venting requirements, installation distance from combustibles, etc.). 8) Please be aware that a separate permit from the fire department will be required for the installation of the propane tank and will need to be completed prior to the completion of this permit. 9) Please provide electrical load calculations per section 106.1.1 of the 2006 IBC. 10) Please specify the conduit and conductor size for the new equipment per section 106.1.1 of the 2006 IBC. 11) Please revise the code analysis to include information regarding the adjacent tenant space and uses per section 106.1.1 of the 2006 IBC. 12) Please provide a framing detail for the installation of the louvers per section 106.1.1 of the 2006 IBC. |
| 07/17/2007 | CHRIS KIEL (WILDAN) | MECHANICAL-COMMERCIAL | REVIEW | Denied | |
| 07/17/2007 | CHRIS KIEL (WILDAN) | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
| 07/17/2007 | CHRIS KIEL (WILDAN) | PLUMBING-COMMERCIAL | REVIEW | Denied |