Permit Number - T07OT01356
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | PRE INSPECTION DONE AT SITE FOR REEVALUATION OF CORRECTION COMMENTS. 1 HOUR INSPECTION FEE ADDED TO ACTIVITY. FOLLOWING ARE NEW PLAN CORRECTION REQUIREMENTS. 1) PROVIDE DETAIL SHEETS TO ADDRESS RECOMMENDATIONS NOTED BY SCHNEIDER & ASSOCIATES JOB # 107064 ON APRIL 5 2007. 2) PROVIDE DETAILS FOR CONSTRUCTION OF NEW 2 HOUR FIRE WALL. 3) PROVIDE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR AS-BUILT CONDITIONS. DEMONSTRATE THAT SAID SYSTEMS MEET CODE PROVISIONS. 4) PROVIDE INFORMATION ON PLANS THAT BUILDING IS 100% ACCESSIBLE OR SHOW HOW $400 (20% OF FEES FOR 3200 SQ FT ADDITION) WILL BE APPLIED TOWARD MAKING FACILITY MORE ACCESSIBLE. 5) SKYLIGHTS WITHIN 10' OF MECHANICAL UNITS MUST HAVE PROTECTIVE GUARD OR COVER TO PREVENT SERVICE PEOPLE FROM FALLING THROUGH. |