Permit Number: T07OT01356
Parcel: 124160350

Address:
727 E 20TH ST

Review Status: Completed

Review Details: C OF O

Permit Number - T07OT01356
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2007 CHUCK STEPHENSON SIGNS REVIEW Approved
06/11/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE STRUCTURAL CALCULATIONS FOR "NEW" STEEL BUILDING.

2. PROVIDE DETAILS FOR WORK DONE WITHOUT PERMITS INCLUDING CONSTRUCTION OF 2 HR WALL, NEW JOIST ATTACHEMENTS, LEDGER ATTACHMENTS, FOOTINGS, TRUSS MODIFICATION FOR STAIR.

3. PROVIDE SPECIAL INSPECTION PROGRAM FOR EPOXY BOLTING, FOOTING ANALYSIS, EXISTING BUILDING ANALYSIS.

4. PROVIDE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR AS-BUILT CONDITIONS. DEMONSTRATE THAT ALL BUILDING SYSTEMS MEET CODE PROVISIONS.

5. PROVIDE INFORMATION PER 2003 IBC THAT BUILDING IS EITHER 100% ACCESSIBLE OR COMPLIANCE WITH 3409.6.
11/20/2008 CPIERCE1 ZONING REVIEW Needs Review