07/09/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Denied DATE: July 9, 2007
SUBJECT: 1320 S Camino Arriba Single Family Residence- Engineering Review
TO: Moses and Ann Tyler
LOCATION: T14S R13E Sec22, Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T07OT01307 (Floodplain Use Permit)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the Floodplain Use Permit (T07OT01307) and Drainage Statement (JE Fuller Hydrology and Geomorphology, Inc., 19OCT06) for the above referenced property and does not recommend approval of the Floodplain Use Permit at this time.

The subject property is partially located within a Special Flood Hazard Area (SFHA), Zone AH as shown on the Flood Insurance Rate Map (FIRM), Community- Panel No. 040073-04019C-2210K, effective date February 8, 1999. Federal law requires that a flood insurance policy be obtained as a condition of a federally backed mortgage or loan that is secured by a building located within a SFHA.

The following information is required:


FUP SITE PLAN: The engineered site plan (stamped by Maverick Gibbons, 07JUN07) was reviewed for floodplain purposes only. A site plan application must be submitted for review prior to site plan review and approval. All information associated with the drainage report and this FUP must be shown on the site plan prior to approval.

1) TC Sec.26-11.2.2: Provide the FEMA AH 100-year floodplain limits on the revised-engineered site plan. The floodplain limit must be shown on the site plan in a surveyable manner.

2) TC Sec.26-8.d: Provide 2 cross sections on the site plan that shows the property lines, fill pad location, single family residence, and elevation limits of existing ground and future fill pad. Cross sections should be shown going through the north-south and east-west property lines. The fill pad and single family residence can not encroach into the 100-year floodplain limits by more than what is shown on the submitted drainage report.

3) DS Sec.11-01.2.I: Provide a grading plan and a grading permit application with all associated details for review and approval prior to site plan approval. The estimated fill quantities on the engineered site plan shows that over 50 cubic yards of material are required in order to elevate the proposed single family residence at or above the regulatory flood elevation. A grading application is required if fill quantities exceed 50 cubic yards. Provide on the grading plan the cut and fill quantities for permit purposes.

4) DS Sec.11-01.8.1: Provide cross sections on the grading plan through the lot and at all property boundaries to verify that differential grading requirements have been satisfied. Cross sections at all property lines are required to show how the fill pad is used to elevate the single family residence without encroaching onto adjacent lots.

5) Revise General Note #6 to call out the correct water surface elevation that is shown in the JE Fuller Drainage Report.

6) Be advised that all future improvements (walls, fences, pool, and detached or attached accessory structures) will require a separate permit and possible drainage report for review and approval.


GENERAL COMMENTS:

Please be advised that since the subject property is located within the SFHA Zone AH floodplain, it will be required that two elevation certificates for the proposed single family residence be filled out by an Arizona Registered Land Surveyor showing that the top of the lowest finished floor and the lowest point of any attached appliances is above the regulatory flood elevation (one foot higher than the calculated water surface elevation of the base flood) prior to the 1010/1015 and Final Inspection and returned to our office.

Please provide the revised engineered site plan, site plan application, grading plan, a grading plan application, and all associated details that address the comments provided above.

If you have any questions, or to schedule a meeting I can be reached at 837-4929.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services