Review Details: FLOODPLAIN

Permit Number - T07OT01254
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: The WLB Group DATE: July 25, 2007
David Little, P.E.
4444 E. Broadway Blvd.
Tucson, Arizona, 85711

SUBJECT: I-10 & Kolb Rd. Subdivision, 6751 E. Hermans Rd.
Floodplain Use Permit T07OT01254 (First Review)
T15S, R15E, Section 19

RESUBMITTAL REQUIRED: Floodplain Use Permit.

The Floodplain use permit (FUP) cannot be approved at this time. Please address the following review comments prior to the next submittal.

Flood plain use permit:

1. Include a detailed response letter to the comments along with the re-submittal of the FUP.
2. The FUP cannot be issued prior to the approval of the Tentative Plat (S06-186) or the Grading Plan (T07BU01190). Re-submit the FUP with the Grading Plan.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/6751 E. Hermans Rd FUP