Permit Number - T07OT01218
Review Name: C OF O
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2007 | ANY | ZONING | REVIEW | Active | |
| 05/23/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE SPECIFY IF THIS USE IS SEPARATED OR NONSEPARATED PER SECTION 106.1.1 OF THE 2003 IBC. 2) PLEASE PROVIDE THE ALLOWABLE AREA CALCULATION IN ORDER TO VERIFY COMPLIANCE WITH CHAPTER 5 OF THE 2003 IBC. 3) PLEASE SPECIFY THE USE OF THE ADJACENT TENANT SPACE TO THE NORTH IN ORDER TO VERIFY COMPLIANCE WITH CHAPTER 3 AND 5 OF THE 2003 IBC. 4) PLEASE REVISE THE APPLICABLE BUILDING CODES TO THOSE CURRENTLY ADOPTED BY THE CITY OF TUCSON PER SECTION 106.1.1 OF THE 2003 IBC (i.e. 2003 IMC, 2002 NEC, 2003 IECC AND 2003 UPC). 5) PLEASE PROVIDE A DRINKING FOUNTAIN PER TABLE 2902.1 OF THE 2003 IBC. 6) PLEASE REVISE THE HEIGHT OF THE BASE IN THE TOILET ROOM PER SECTION 1210.1 OF THE 2003 IBC. |
| 05/23/2007 | CHUCK STEPHENSON | SIGNS | REVIEW | Approved |