Permit Number: T07OT01171
Parcel: 113082980

Review Status: Completed

Review Details: C OF O

Permit Number - T07OT01171
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2006 HEATHER THRALL ZONING REVIEW Approved
01/27/2006 JULIE YBARRA SIGNS REVIEW Approved
05/29/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE COPY OF LAST CITY OF TUCSON APPROVED PLAN.

2) NEW PLANS TO BE SEALED BY STATE OF ARIZONA REGISTERED DESIGN PROFESSIONAL.

3) SHOW ACCESSIBLE ROUTE FROM SITE ARRIVAL POINT AND WITHIN THE SITE PER SECTION 1104 OF 2003 INTERNATIONAL BUILDING CODE AND ANSI 117.1.

4) DWELLING AND SLEEPING UNITS MUST COMPLY WITH SECTION 1107.6.4 OF 2003 IBC. PLEASE REFER TO ANSI 117.1 FOR DETAILS ON DOOR WIDTHS, CLEAR FLOOR SPACES, HARDWARE HEIGHTS AND OTHER ACCESSIBILITY REQUIREMENTS.

5) PROVIDE EMERGENCY EGRESS LIGHTING PER SECTION 1006 OF THE IBC.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2007 GERARDO BONILLA APPROVAL SHELF Completed
06/13/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
06/13/2007 GERARDO BONILLA REJECT SHELF Completed