Permit Number: T07OT00791
Parcel: 11613211D

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T07OT00791
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2007 LOREN MAKUS ENGINEERING REVIEW Denied May 17, 2007
Engineering Review for T07CM01155 and T07OT00791
1833 W Speedway

The application for a floodplain use permit cannot be approved at this time. The encroachment analysis for the project must be revised and additional hydraulic information must be provided.

1. Indicate the basis of elevation for the water surface elevation determined in the report. Provide a benchmark location that can be used for the elevation certificate required for the proposed house. Indicate the source of the contours that were used for the analysis.
2. Revise the Mannings analysis to use a roughness coefficient in the range of 0.060 to 0.80 as shown in table 8.1 of the Standards Manual for Drainage Design and Floodplain Management in Tucson Arizona.
3. Provide an exhibit or exhibits showing water surface contours in at least two locations. The water surface contours must be provided for both existing and proposed conditions.
4. Provide a discussion of the erosion hazard setback from the Mosaic Wash. If the proposed structure is within the EHS, suitable erosion protection must be provided.


The Site Plan must revised to provide the following information:

5. Provide a delineation of the area subject to flooding in a 100-year event. This must be in addition to the plotted FEMA flood zone delineation. The area inside the delineated floodprone area must be labeled as "Protected Riparian Area" and must remain undisturbed by development unless approval is received through the overlay review process.
6. Provide a delineation of the erosion hazard setback on the site plan.
7. Provide a note indicating the basis of elevation for the base flood elevation and describing a benchmark for the basis of elevation.
8. Provide a description of the existing easement shown on the site plan. Provide recordation data for the easement.
9. The site plan shows proposed water and sewer connections that may be within the protected riparian area. Utility installation may be allowed within the protected riparian area but will require the overlay review process.

Please revise the site plan and provide a new report addressing these comments. Include a detailed response letter indicating how each comment has been addressed.

If you have any questions or to set up a meeting, contact me at loren.makus@tucsonaz.gov or at 520.837.4927.

Loren Makus, E.I.T
Senior Engineering Associate