Review Details: FLOODPLAIN
Permit Number - T07OT00785
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: May 21, 2007 ACTIVITY NUMBER: T07OT00785 / T07CM00100 PROJECT NAME: Ilzar Residence Garage/Workshop PROJECT ADDRESS: 8831 East Shiloh Place PROJECT REVIEWER: Patricia Gilbert FLOODPLAIN USE PERMIT IS DENIED RESUBMITTAL REQUIRED: SITE PLAN, , FLOODPLAIN USE PERMIT APPLICATION HYDROLOGY REPORT IS APPROVED 1. The submitted Hydrology Report shows the erosion hazard setback (EHS) at 8.4' from the property line. The site plan shows the addition 6.8' from the property line. Structures can not be placed with the EHS. The addition must placed outside the EHS. This office recommends to place the addition 9' from the property line. Revise the site plan to show the addition outside the EHS. 2. Provide a general note to the site plan stating this property is subject the Floodplain Ordinance Chapter 26. |