Permit Number: T07OT00402
Parcel: 111071150

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T07OT00402
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: March 8, 2007
ACTIVITY NUMBER: T07OT00402 / T07CM00299
PROJECT ADDRESS: 2607 North Sparkman Blvd.
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, FLOODPLAIN USE PERMIT APPLICATION, COST ESTIMATE

1. Any structure which is substantially improved at a cost equal to or exceeding 50% of the full cash value of the structure as shown on the latest assessment rolls from the county assessor or an appraisal from a licensed appraiser with the State of Arizona. The submitted cost estimate exceeds 50% of the value of the structure. The value of the structure based on the submitted appraisal is $71,238. The submitted construction cost estimate was 40,275, equals to a 57% increase in flood damage potential. The Permits Plus system estimated the construction cost at 47,272, equals to a 66% increase in flood damage potential. The proposed addition is considered a "substantial improvement," and must meet the floodplain requirements found in Chapter 26.

There are two solutions:

1) Reduce the scope of the project to bring the cost of construction down so the project is not a substantial improvement.
2) Elevate the addition to be one foot above the established water surface elevation.

2. Add a general note to the plan that the entire property lies within a City of Tucson Regulatory flood hazard area. DS 2-02.2.1.A.15.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/23/2007 SUE REEVES REJECT SHELF Completed