Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2007 JASON GREEN ENGINEERING REVIEW Approved January 16, 2007
FLOODPLAIN USE PERMIT # T07OT00068
PROJECT ADDRESS: 6525 S Country Club Road
APPLICANT'S NAME: WLB Group
PROPERTY OWNER: Valencia Tucson LLC


The work permitted for this site plan and grading plan is located within the a mapped 100-year floodplain per the drainage report prepared by The WLB Group, dated January 7, 2007. The applicant is authorized to use a portion of the flood hazard area in the City of Tucson, Arizona, on the property described as:

6525 S Country Club Road, Tucson, AZ 85706 in a portion of Township 15 South, Range 14 East, Section 16, for the purpose of constructing a new hotel (Hilton Garden Inn) as shown on the approved site plan (T06CM03798) and grading plan (T06BU01659).

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.


The following 8 conditions apply to this permit:
1) This permit becomes invalid and is subject to additional floodplain review, if any required development changes the configuration of the approved site plan or grading plan, or if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from constructing the proposed hotel within the mapped regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.
2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
3) All work shall conform to the approved Details and grading plan sheets for Hilton Garden Inn, which are made part of this permit.
4) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T07OT00068 FOR INFORMATION PLEASE CALL 791-5550."
5) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times.
6) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.
7) There shall be no stockpiling material, or storage of vehicles, other than that which is accepted by COT and as shown on the approved plans. There shall be no stockpiling or disturbance outside of disturbance limits. Construction material and vehicles shall be promptly removed once installation and construction is complete.
8) Contractor will need to call for floodplain use permit inspections by Development Services Department Engineering Division Inspection Team (791-5550) prior to and after the construction of the proposed hotel.


This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Division.

(EXPIRATION DATE) Month: 01 Day: 20 Year: 2008

APPLICANT/CONTRACTOR: The WLB Group
ADDRESS: 4444 E Broadway Blvd, Tucson, Arizona 85711
PHONE: (520) 881-7480
OWNER: Valencia Tucson LLC
ADDRESS: 10985 Cody St, Ste 220, Overland, KS 66210
PHONE: Not listed on application


SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2007 FSANCHE1 OUT TO CUSTOMER Completed