Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL02233
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07EL02233 12/28/07 1. Specify motor type on plans. Cut sheets call for Explosion-Proof Option to be powered at 230V, and plans call for a single-pole circuit. 2. Provide Trailer panel schedule and load calculations. 3. Provide supply voltage and verify that it is 240V. |