Permit Number: T07EL02233
Parcel: 141220240

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL02233
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07EL02233 12/28/07

1. Specify motor type on plans. Cut sheets call for Explosion-Proof Option to be powered at 230V, and plans call for a single-pole circuit.
2. Provide Trailer panel schedule and load calculations.
3. Provide supply voltage and verify that it is 240V.