Permit Number: T07EL02226
Parcel: 117041440

Address:
610 N 9TH AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL02226
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07EL02226 12/27/07

1. It is our understanding from the tenant that the scope of work only entails changing out an existing panel, terminating existing circuits on to this new panel, and providing a new service. From the plans it appears as a totally new buildout. Please clarify. If this is to be a new buildout, we will have to address the possibility of a classified location. If the area is already permitted for all this equipment, work with John Williams to demonstrate Certificate of Occupancy.
2. Regarding Keynote 4, if this is a new supply to a paint spray booth, we may have to consider a classified location and more information. Please clarify.
3. On the Line Diagram, there are two panels L1.
4. Fault current analysis directs the contractor to provide Panel L1. It appears that the scope only deals with L2. Please clarify.