Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL02099
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/03/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide City DSD Activity Number(s) for applicable construction projects, and have Permit Clerks cross-reference. 2. Provide conductor size for run on Keynote 33. Important for evaluation per NRC 240.21 (C) (4) (2) and 250.32. 3. Information for Panels A and B, as MLO panels, is not sufficient to determine secondary protection for the transformers, or compliance with NEC 240.21 (C) (2) (1) (a) and (b). Please note that if conductor size is to be increased, sizing of the Grounding Electrode Conductor may need to be revisited. 4. Please provide a disconnecting means on the building per NEC 225.32. 5. Conduits on Keynotes 13 and 14 have a redundant GROUND. Reference NEC 250.24 (C). |