Review Details: ELECTRICAL
Permit Number - T07EL01936
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07EL01936 11/1/07 1. Protect ungrounded service conductors according to the requirements of NEC 230.90 (A). 2. Please eliminate the redundant #8 GND on the line side of the service disconnecting means. 3. Add the following note to the plans: "Contractor shall provide electrical inspector TEP Available Fault Current before final electrical clearance. 4. Add Zoning and Engineering to WorkFlow. |