Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL01815
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07EL01815 10/24/07 1. Panel location appears to be at a different building from that which the lights are to be mounted on panel on plans. This violates NEC 225.30, in the case where the second building already has electrical power. 2. Provide the schedule required by Tucson Lighting Code Section 8.1 Item #6. THIS COMMENT WAS MADE ON THE FIRST REVIEW. Note that if you intend to use full cutoff fixtures, this needs to be obvious from manufacturer cut sheets. |