Permit Number: T07EL01815
Parcel: 106042430

Address:
202 E MOHAVE RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL01815
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07EL01815 10/9/07

1. Provide panel and circuit number for new lighting fixtures.
2. Provide panel load calculations.
3. Indicate location of panel on plans.
4. Provide manufacturer data to certify mean lumens per fixture.
5. Specify conduit and conductor size and type.
6. Provide the schedule required by Tucson Lighting Code Section 8.1 Item #6.