Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL01815
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07EL01815 10/9/07 1. Provide panel and circuit number for new lighting fixtures. 2. Provide panel load calculations. 3. Indicate location of panel on plans. 4. Provide manufacturer data to certify mean lumens per fixture. 5. Specify conduit and conductor size and type. 6. Provide the schedule required by Tucson Lighting Code Section 8.1 Item #6. |