Permit Number: T07EL01687
Parcel: 141332420

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL01687
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07EL01687 11/2/07

1. Add Zoning and Engineering to WorkFlow.
2. If pump was approved on other permitted drawings, provide Activity Number such that we can cross-reference, and show pump as "On Other Permit" on plans.
3. Show location of pump, disconnecting means, and service disconnect on plans.
4. Specify Grounding Electode System.
5. Show overcurrent protection for pump.
6. Provide electrical line diagram.
7. Provide fault current rating of new equipment.