Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL01687
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07EL01687 11/2/07 1. Add Zoning and Engineering to WorkFlow. 2. If pump was approved on other permitted drawings, provide Activity Number such that we can cross-reference, and show pump as "On Other Permit" on plans. 3. Show location of pump, disconnecting means, and service disconnect on plans. 4. Specify Grounding Electode System. 5. Show overcurrent protection for pump. 6. Provide electrical line diagram. 7. Provide fault current rating of new equipment. |