Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL01372
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07EL01372 7/25/07 1. All sheets shall be on same sized paper. 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 3. Show location of all new and existing equipment on plan view. 4. Show fault current ratings of existing panels. 5. Size BONDs on the line side of the service disconnect per NEC Table 250.66. Reference NEC 250.102 (C). 6. 350 kcmil has ampacity of 310A. Not protected by the 400 AF. |