Permit Number: T07EL01372
Parcel: 14027046F

Address:
2660 E GANLEY RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL01372
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07EL01372 7/25/07

1. All sheets shall be on same sized paper.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Show location of all new and existing equipment on plan view.
4. Show fault current ratings of existing panels.
5. Size BONDs on the line side of the service disconnect per NEC Table 250.66. Reference NEC 250.102 (C).
6. 350 kcmil has ampacity of 310A. Not protected by the 400 AF.